Schneider TeSys D contactor 3P 40A AC-3 up to 440V coil 100-250V AC/DC EverLink
# of Pole : 3
Arus Pengenal (A) : 40A
Coil AC/DC : 110-250V (KUE)
Rp 2,669,193.00
44.00 %
Rp 4,766,417.00
Rp 4,766,417.00
Option not available
[Deskripsi] 1. product name : TeSys D Green 2. product or component type : Contactor 3. device short name : LC1D 4. contactor application : -Motor control -Resistive load 5. utilisation category : -AC-1 -AC-3 6. poles description : 3P 7. power pole contact composition : 3 NO 8. [Ue] rated operational voltage : Power circuit: <= 690 V AC 25...400 Hz 9. [Ie] rated operational current : -60 A (at <60 °C) at <= 440 V AC-1 for power circuit -40 A (at <60 °C) at <= 440 V AC-3 for power circuit 10. motor power kW : -11 kW at 220...230 V AC 50 Hz (AC-3) -18.5 kW at 380...400 V AC 50 Hz (AC-3) -22 kW at 415 V AC 50 Hz (AC-3) -22 kW at 440 V AC 50 Hz (AC-3) -22 kW at 500 V AC 50 Hz (AC-3) -30 kW at 660...690 V AC 50 Hz (AC-3) 11. motor power HP (UL / CSA) : -3 hp at 115 V AC 60 Hz for 1 phase motors -5 hp at 230/240 V AC 60 Hz for 1 phase motors -10 hp at 200/208 V AC 60 Hz for 3 phases motors -10 hp at 230/240 V AC 60 Hz for 3 phases motors -30 hp at 460/480 V AC 60 Hz for 3 phases motors -30 hp at 575/600 V AC 60 Hz for 3 phases motors 12. [Uc] control circuit voltage : -100...250 V AC 50/60 Hz -100...250 V DC 13. coil type : AC/DC electronic 14. auxiliary contact composition : 1 NO + 1 NC 15. [Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947 16. overvoltage category : III 17. [Ith] conventional free air thermal current : -10 A (at 60 °C) for signalling circuit -25 A (at 60 °C) for power circuit 18. Irms rated making capacity : -250 A at 440 V for power circuit conforming to IEC 60947 -140 A AC for signalling circuit conforming to IEC 60947-5-1 -250 A DC for signalling circuit conforming to IEC 60947-5-1 19. rated breaking capacity : 250 A at 440 V for power circuit conforming to IEC 60947 20. [Icw] rated short-time withstand current : -100 A - 1 s for signalling circuit -120 A - 500 ms for signalling circuit -140 A - 100 ms for signalling circuit -30 A 40 °C - 10 min for power circuit -61 A 40 °C - 1 min for power circuit -105 A 40 °C - 10 s for power circuit -210 A 40 °C - 1 s for power circuit 21. associated fuse rating : -10 A gG for signalling circuit conforming to IEC 60947-5-1 -25 A gG at <= 690 V coordination type 1 for power circuit -20 A gG at <= 690 V coordination type 2 for power circuit 22. average impedance : 2.5 mOhm - Ith 25 A 50 Hz for power circuit 23. [Ui] rated insulation voltage : -Power circuit: 690 V conforming to IEC 60947-4-1 -Signalling circuit: 690 V conforming to IEC 60947-1 24. electrical durability : -2.4 Mcycles 8 A AC-3 at Ue <= 440 V -0.6 Mcycles 25 A AC-1 at Ue <= 440 V 25. power dissipation per pole : -1.56 W AC-1 -0.2 W AC-3 26. safety cover : With 27. mounting support : -Rail -Plate 28. standards : -EN/IEC 60947-4-1 -EN/IEC 60947-5-1 -UL 60947-4-1 -CSA C22.2 No 60947-4-1 29. product certifications : -CCC -CSA -EAC -UL -KC -DNV-GL -LROS (Lloyds register of shipping) 30. connections - terminals : -Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end -Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end -Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end -Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end -Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid -Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid -Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end -Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end -Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end -Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end -Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid -Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid 31. tightening torque : -Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm -Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 -Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm -Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 32. operating time : -45...55 ms closing -20...90 ms opening 33. safety reliability level : -B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 -B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 34. mechanical durability : 15 Mcycles 35. maximum operating rate : 3600 cyc/h 60 °C 36. coil technology : Built-in bidirectional peak limiting control circuit voltage limits 37. <= 0.1 Uc 60 °C drop-out : -0.85...1.1 Uc 60 °C operational AC -0.8...1.2 Uc 60 °C operational DC 38. inrush power in VA : 15 VA 50/60 Hz (at 20 °C) 39. inrush power in W : 14 W at 20 °C 40. hold-in power consumption in VA : 0.9 VA (at 20 °C) 50/60 Hz 41. hold-in power consumption in W : 0.6 W at 20 °C 42. heat dissipation : 0.6 W at 50/60 Hz 43. auxiliary contacts type : -type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 -type mirror contact 1 NC conforming to IEC 60947-4-1 44. signalling circuit frequency : 25...400 Hz 45. minimum switching current : 5 mA for signalling circuit 46. minimum switching voltage : 17 V for signalling circuit 47. non-overlap time : -1.5 ms on de-energisation between NC and NO contact -1.5 ms on energisation between NC and NO contact 48. insulation resistance : > 10 MOhm for signalling circuit 49. IP degree of protection : IP20 front face conforming to IEC 60529 50. protective treatment : TH conforming to IEC 60068-2-30 51. pollution degree : 3 52. ambient air temperature for operation : -25…60 °C 53. ambient air temperature for storage : -60…80 °C 54. permissible ambient air temperature around the device : -40…70 °C at Uc 55. operating altitude : 3000 m without 56. fire resistance : 850 °C conforming to IEC 60695-2-1 57. flame retardance : V1 conforming to UL 94 58. mechanical robustness : -Vibrations contactor open: 2 Gn, 5...300 Hz -Vibrations contactor closed: 4 Gn, 5...300 Hz -Shocks contactor open: 10 Gn for 11 ms -Shocks contactor closed: 15 Gn for 11 ms 59. height : 122 mm 60. width : 55 mm 61. depth : 120 mm 62. product weight : 0.992 kg 63. colour : -Grey (SE GREY 6) -Green (SE GREEN 2)
range | TeSys | |
---|---|---|
product name | TeSys D Green | |
product or component type | Contactor | |
device short name | LC1D | |
contactor application | Resistive load Motor control | |
utilisation category | AC-1 AC-3 | |
poles description | 3P | |
power pole contact composition | 3 NO | |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 25...400 Hz | |
[Ie] rated operational current | 60 A (at <60 °C) at <= 440 V AC-1 for power circuit 40 A (at <60 °C) at <= 440 V AC-3 for power circuit | |
motor power kW | 11 kW at 220...230 V AC 50 Hz (AC-3) 18.5 kW at 380...400 V AC 50 Hz (AC-3) 22 kW at 415 V AC 50 Hz (AC-3) 22 kW at 440 V AC 50 Hz (AC-3) 22 kW at 500 V AC 50 Hz (AC-3) 30 kW at 660...690 V AC 50 Hz (AC-3) | |
motor power HP (UL / CSA) | 3 hp at 115 V AC 60 Hz for 1 phase motors 5 hp at 230/240 V AC 60 Hz for 1 phase motors 10 hp at 200/208 V AC 60 Hz for 3 phases motors 10 hp at 230/240 V AC 60 Hz for 3 phases motors 30 hp at 460/480 V AC 60 Hz for 3 phases motors 30 hp at 575/600 V AC 60 Hz for 3 phases motors | |
[Uc] control circuit voltage | 100...250 V AC 50/60 Hz 100...250 V DC | |
coil type | AC/DC electronic | |
auxiliary contact composition | 1 NO + 1 NC | |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | |
overvoltage category | III | |
[Ith] conventional free air thermal current | 60 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit | |
Irms rated making capacity | 800 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 | |
rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 | |
[Icw] rated short-time withstand current | 72 A 40 °C - 10 min for power circuit 165 A 40 °C - 1 min for power circuit 320 A 40 °C - 10 s for power circuit 720 A 40 °C - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit | |
associated fuse rating | 80 A gG at <= 690 V coordination type 1 for power circuit 80 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1 | |
average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit | |
[Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1 | |
electrical durability | 2 Mcycles 35 A AC-3 at Ue <= 440 V 0.7 Mcycles 60 A AC-1 at Ue <= 440 V | |
power dissipation per pole | 5.4 W AC-1 2.4 W AC-3 | |
Front cover | With | |
mounting support | Plate Rail | |
standards | EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 | |
product certifications | CCC CSA EAC UL KC DNV-GL LROS (Lloyds register of shipping) | |
connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible without cable end Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible with cable end Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²solid Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible without cable end Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible with cable end Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²solid | |
tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm | |
operating time | 55...65 ms closing 20...120 ms opening (date code >= 17221) 20...80 ms opening (date code >= 18011) | |
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
mechanical durability | 6 Mcycles | |
maximum operating rate | 3600 cyc/h 60 °C |
coil technology | Built-in bidirectional peak limiting | |
---|---|---|
control circuit voltage limits | <= 0.1 Uc (-40…70 °C):drop-out AC/DC 0.85...1.1 Uc (-40…60 °C):operational AC/DC 1...1.1 Uc (60…70 °C):operational AC/DC | |
inrush power in VA | 18 VA 50/60 Hz (at 20 °C) | |
inrush power in W | 14 W at 20 °C | |
hold-in power consumption in VA | 1.8 VA (at 20 °C) 50/60 Hz | |
hold-in power consumption in W | 1.2 W at 20 °C | |
heat dissipation | 1.2 W at 50/60 Hz | |
auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 | |
signalling circuit frequency | 25...400 Hz | |
minimum switching current | 5 mA for signalling circuit | |
minimum switching voltage | 17 V for signalling circuit | |
non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact | |
insulation resistance | > 10 MOhm for signalling circuit |
IP degree of protection | IP20 front face conforming to IEC 60529 | |
---|---|---|
protective treatment | TH conforming to IEC 60068-2-30 | |
pollution degree | 3 | |
ambient air temperature for operation | -40…60 °C 60…70 °C with derating | |
ambient air temperature for storage | -60…80 °C | |
operating altitude | 0...3000 m | |
fire resistance | 850 °C conforming to IEC 60695-2-1 | |
flame retardance | V1 conforming to UL 94 | |
mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms | |
height | 122 mm | |
width | 55 mm | |
depth | 120 mm | |
net weight | 0.992 kg | |
colour | Grey (SE GREY 6) Green (SE GREEN 2) |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 1.067 kg | |
Package 1 Height | 6.5 cm | |
Package 1 width | 13.7 cm | |
Package 1 Length | 15.2 cm |
Sustainable offer status | Green Premium product | |
---|---|---|
REACh Regulation | ||
EU RoHS Directive | Compliant EU RoHS Declaration | |
Mercury free | Yes | |
RoHS exemption information | ||
China RoHS Regulation | China RoHS declaration Product out of China RoHS scope. Substance declaration for your information | |
Environmental Disclosure | ||
Circularity Profile | ||
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins | |
Halogen content performance | Halogen free plastic parts & cables product |
Warranty | 12 months |
---|
Specifications for Schneider TeSys D contactor 3P 40A AC-3 up to 440V coil 100-250V AC/DC EverLink
General Information | |
---|---|
# of Pole | 3 |
Arus Pengenal (A) | 40A |
Uncategorized | |
Coil AC/DC | 110-250V (KUE) |
[Deskripsi] 1. product name : TeSys D Green 2. product or component type : Contactor 3. device short name : LC1D 4. contactor application : -Motor control -Resistive load 5. utilisation category : -AC-1 -AC-3 6. poles description : 3P 7. power pole contact composition : 3 NO 8. [Ue] rated operational voltage : Power circuit: <= 690 V AC 25...400 Hz 9. [Ie] rated operational current : -60 A (at <60 °C) at <= 440 V AC-1 for power circuit -40 A (at <60 °C) at <= 440 V AC-3 for power circuit 10. motor power kW : -11 kW at 220...230 V AC 50 Hz (AC-3) -18.5 kW at 380...400 V AC 50 Hz (AC-3) -22 kW at 415 V AC 50 Hz (AC-3) -22 kW at 440 V AC 50 Hz (AC-3) -22 kW at 500 V AC 50 Hz (AC-3) -30 kW at 660...690 V AC 50 Hz (AC-3) 11. motor power HP (UL / CSA) : -3 hp at 115 V AC 60 Hz for 1 phase motors -5 hp at 230/240 V AC 60 Hz for 1 phase motors -10 hp at 200/208 V AC 60 Hz for 3 phases motors -10 hp at 230/240 V AC 60 Hz for 3 phases motors -30 hp at 460/480 V AC 60 Hz for 3 phases motors -30 hp at 575/600 V AC 60 Hz for 3 phases motors 12. [Uc] control circuit voltage : -100...250 V AC 50/60 Hz -100...250 V DC 13. coil type : AC/DC electronic 14. auxiliary contact composition : 1 NO + 1 NC 15. [Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947 16. overvoltage category : III 17. [Ith] conventional free air thermal current : -10 A (at 60 °C) for signalling circuit -25 A (at 60 °C) for power circuit 18. Irms rated making capacity : -250 A at 440 V for power circuit conforming to IEC 60947 -140 A AC for signalling circuit conforming to IEC 60947-5-1 -250 A DC for signalling circuit conforming to IEC 60947-5-1 19. rated breaking capacity : 250 A at 440 V for power circuit conforming to IEC 60947 20. [Icw] rated short-time withstand current : -100 A - 1 s for signalling circuit -120 A - 500 ms for signalling circuit -140 A - 100 ms for signalling circuit -30 A 40 °C - 10 min for power circuit -61 A 40 °C - 1 min for power circuit -105 A 40 °C - 10 s for power circuit -210 A 40 °C - 1 s for power circuit 21. associated fuse rating : -10 A gG for signalling circuit conforming to IEC 60947-5-1 -25 A gG at <= 690 V coordination type 1 for power circuit -20 A gG at <= 690 V coordination type 2 for power circuit 22. average impedance : 2.5 mOhm - Ith 25 A 50 Hz for power circuit 23. [Ui] rated insulation voltage : -Power circuit: 690 V conforming to IEC 60947-4-1 -Signalling circuit: 690 V conforming to IEC 60947-1 24. electrical durability : -2.4 Mcycles 8 A AC-3 at Ue <= 440 V -0.6 Mcycles 25 A AC-1 at Ue <= 440 V 25. power dissipation per pole : -1.56 W AC-1 -0.2 W AC-3 26. safety cover : With 27. mounting support : -Rail -Plate 28. standards : -EN/IEC 60947-4-1 -EN/IEC 60947-5-1 -UL 60947-4-1 -CSA C22.2 No 60947-4-1 29. product certifications : -CCC -CSA -EAC -UL -KC -DNV-GL -LROS (Lloyds register of shipping) 30. connections - terminals : -Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end -Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end -Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end -Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end -Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid -Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid -Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end -Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end -Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end -Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end -Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid -Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid 31. tightening torque : -Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm -Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 -Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm -Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 32. operating time : -45...55 ms closing -20...90 ms opening 33. safety reliability level : -B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 -B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 34. mechanical durability : 15 Mcycles 35. maximum operating rate : 3600 cyc/h 60 °C 36. coil technology : Built-in bidirectional peak limiting control circuit voltage limits 37. <= 0.1 Uc 60 °C drop-out : -0.85...1.1 Uc 60 °C operational AC -0.8...1.2 Uc 60 °C operational DC 38. inrush power in VA : 15 VA 50/60 Hz (at 20 °C) 39. inrush power in W : 14 W at 20 °C 40. hold-in power consumption in VA : 0.9 VA (at 20 °C) 50/60 Hz 41. hold-in power consumption in W : 0.6 W at 20 °C 42. heat dissipation : 0.6 W at 50/60 Hz 43. auxiliary contacts type : -type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 -type mirror contact 1 NC conforming to IEC 60947-4-1 44. signalling circuit frequency : 25...400 Hz 45. minimum switching current : 5 mA for signalling circuit 46. minimum switching voltage : 17 V for signalling circuit 47. non-overlap time : -1.5 ms on de-energisation between NC and NO contact -1.5 ms on energisation between NC and NO contact 48. insulation resistance : > 10 MOhm for signalling circuit 49. IP degree of protection : IP20 front face conforming to IEC 60529 50. protective treatment : TH conforming to IEC 60068-2-30 51. pollution degree : 3 52. ambient air temperature for operation : -25…60 °C 53. ambient air temperature for storage : -60…80 °C 54. permissible ambient air temperature around the device : -40…70 °C at Uc 55. operating altitude : 3000 m without 56. fire resistance : 850 °C conforming to IEC 60695-2-1 57. flame retardance : V1 conforming to UL 94 58. mechanical robustness : -Vibrations contactor open: 2 Gn, 5...300 Hz -Vibrations contactor closed: 4 Gn, 5...300 Hz -Shocks contactor open: 10 Gn for 11 ms -Shocks contactor closed: 15 Gn for 11 ms 59. height : 122 mm 60. width : 55 mm 61. depth : 120 mm 62. product weight : 0.992 kg 63. colour : -Grey (SE GREY 6) -Green (SE GREEN 2)
range | TeSys | |
---|---|---|
product name | TeSys D Green | |
product or component type | Contactor | |
device short name | LC1D | |
contactor application | Resistive load Motor control | |
utilisation category | AC-1 AC-3 | |
poles description | 3P | |
power pole contact composition | 3 NO | |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 25...400 Hz | |
[Ie] rated operational current | 60 A (at <60 °C) at <= 440 V AC-1 for power circuit 40 A (at <60 °C) at <= 440 V AC-3 for power circuit | |
motor power kW | 11 kW at 220...230 V AC 50 Hz (AC-3) 18.5 kW at 380...400 V AC 50 Hz (AC-3) 22 kW at 415 V AC 50 Hz (AC-3) 22 kW at 440 V AC 50 Hz (AC-3) 22 kW at 500 V AC 50 Hz (AC-3) 30 kW at 660...690 V AC 50 Hz (AC-3) | |
motor power HP (UL / CSA) | 3 hp at 115 V AC 60 Hz for 1 phase motors 5 hp at 230/240 V AC 60 Hz for 1 phase motors 10 hp at 200/208 V AC 60 Hz for 3 phases motors 10 hp at 230/240 V AC 60 Hz for 3 phases motors 30 hp at 460/480 V AC 60 Hz for 3 phases motors 30 hp at 575/600 V AC 60 Hz for 3 phases motors | |
[Uc] control circuit voltage | 100...250 V AC 50/60 Hz 100...250 V DC | |
coil type | AC/DC electronic | |
auxiliary contact composition | 1 NO + 1 NC | |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | |
overvoltage category | III | |
[Ith] conventional free air thermal current | 60 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit | |
Irms rated making capacity | 800 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 | |
rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 | |
[Icw] rated short-time withstand current | 72 A 40 °C - 10 min for power circuit 165 A 40 °C - 1 min for power circuit 320 A 40 °C - 10 s for power circuit 720 A 40 °C - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit | |
associated fuse rating | 80 A gG at <= 690 V coordination type 1 for power circuit 80 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1 | |
average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit | |
[Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1 | |
electrical durability | 2 Mcycles 35 A AC-3 at Ue <= 440 V 0.7 Mcycles 60 A AC-1 at Ue <= 440 V | |
power dissipation per pole | 5.4 W AC-1 2.4 W AC-3 | |
Front cover | With | |
mounting support | Plate Rail | |
standards | EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 | |
product certifications | CCC CSA EAC UL KC DNV-GL LROS (Lloyds register of shipping) | |
connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible without cable end Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible with cable end Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²solid Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible without cable end Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible with cable end Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²solid | |
tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm | |
operating time | 55...65 ms closing 20...120 ms opening (date code >= 17221) 20...80 ms opening (date code >= 18011) | |
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
mechanical durability | 6 Mcycles | |
maximum operating rate | 3600 cyc/h 60 °C |
coil technology | Built-in bidirectional peak limiting | |
---|---|---|
control circuit voltage limits | <= 0.1 Uc (-40…70 °C):drop-out AC/DC 0.85...1.1 Uc (-40…60 °C):operational AC/DC 1...1.1 Uc (60…70 °C):operational AC/DC | |
inrush power in VA | 18 VA 50/60 Hz (at 20 °C) | |
inrush power in W | 14 W at 20 °C | |
hold-in power consumption in VA | 1.8 VA (at 20 °C) 50/60 Hz | |
hold-in power consumption in W | 1.2 W at 20 °C | |
heat dissipation | 1.2 W at 50/60 Hz | |
auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 | |
signalling circuit frequency | 25...400 Hz | |
minimum switching current | 5 mA for signalling circuit | |
minimum switching voltage | 17 V for signalling circuit | |
non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact | |
insulation resistance | > 10 MOhm for signalling circuit |
IP degree of protection | IP20 front face conforming to IEC 60529 | |
---|---|---|
protective treatment | TH conforming to IEC 60068-2-30 | |
pollution degree | 3 | |
ambient air temperature for operation | -40…60 °C 60…70 °C with derating | |
ambient air temperature for storage | -60…80 °C | |
operating altitude | 0...3000 m | |
fire resistance | 850 °C conforming to IEC 60695-2-1 | |
flame retardance | V1 conforming to UL 94 | |
mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms | |
height | 122 mm | |
width | 55 mm | |
depth | 120 mm | |
net weight | 0.992 kg | |
colour | Grey (SE GREY 6) Green (SE GREEN 2) |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 1.067 kg | |
Package 1 Height | 6.5 cm | |
Package 1 width | 13.7 cm | |
Package 1 Length | 15.2 cm |
Sustainable offer status | Green Premium product | |
---|---|---|
REACh Regulation | ||
EU RoHS Directive | Compliant EU RoHS Declaration | |
Mercury free | Yes | |
RoHS exemption information | ||
China RoHS Regulation | China RoHS declaration Product out of China RoHS scope. Substance declaration for your information | |
Environmental Disclosure | ||
Circularity Profile | ||
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins | |
Halogen content performance | Halogen free plastic parts & cables product |
Warranty | 12 months |
---|